Apollo 55000-774MAR XP95 Marine DIN-Rail Input/Output Module
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFInstallation ManualMarine DIN Rail Input/Output Unit Installation Manual
EnglishIncludes a wiring diagramPDFCertification
MED EC Type Examination Certificate (Module B)
EnglishPDFCertification
MED EC Quality System Certificate (Module D)
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
This module is used for input and output connections in XP95 fire detection systems. It features a volt-free single-pole changeover relay output, a monitored switch input and a polarity-independent optocoupler input. It mounts on a standard 35 mm DIN rail and is rated SIL2.
Key features
- Volt-free single-pole changeover relay output
- One monitored switch input
- Polarity-independent, unmonitored optocoupler input
- Reports fault, switch open and switch closed states
- Three visible LEDs
- Mounts on a 35 mm DIN rail
Technical specifications
| Relay switching capacity | Up to 1 A at 30 V DC |
|---|---|
| Supply voltage | 17–28 V DC |
| Standby current | 31.200 µA (tested at 28 V DC) |
| Power-up inrush current | 3,5 mA |
| Maximum operating temperature | 70 °C |
| Relative humidity | 0–95%; without condensation or icing |
| Protection rating | IP20 |
| Warranty | 10 years |
| Approvals | ESC, MED |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other Apollo products

Apollo 29600-378 Conventional I.S. Galvanic Barrier

Apollo 29600-442 Conventional I.S. AV Galvanic Barrier

Apollo 55000-181MAR XP95 Marine DIN-Rail Audible/Visual Alarm Control Module (8 A)

Apollo 55000-182APO DIN-Rail Audible-Visual Warning Control Module
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.