Monday – Friday 09:00 – 18:00Service across Türkiye
Request a Survey / Quote TR
Apollo 55000-812APO Isolated DIN-Rail Zone Monitor Module
Apollo · Contact and Monitoring Modules

Apollo 55000-812APO Isolated DIN-Rail Zone Monitor Module

Brand
Apollo
Model
55000-812APO
Product type
Apollo Fire Alarm Module
Category
Contact and Monitoring Modules
Other spellings
55000812APO, 55000 812APO
System Type
Addressable

Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.

Product description

The XP95 DIN-rail zone monitoring module powers and controls a zone comprising up to 20 Apollo Series 65, Orbis or equivalent conventional fire detectors. It reports the zone status to the fire alarm control panel, allowing conventional detectors to be added to addressable systems. Designed for DIN-rail mounting.

Key features

  • Supports a zone with up to 20 conventional detectors
  • Reports the zone status to the fire alarm control panel
  • Adds a conventional detection zone to addressable systems
  • Suitable for DIN rail mounting
  • Compatible with XP95 and Discovery systems
  • Certified to EN 54-17 and EN 54-18

Technical specifications

Supply voltage17–28 V DC
Maximum start-up time4 seconds
Operating temperature-20 to 70 °C
Relative humidity0–95% (non-condensing or non-icing)
Protection ratingIP20
Dimensions (L × W × D)110 × 107 × 20 mm
Weight95 g
ColourGreen
StandardsEN 54-17, EN 54-18
ApprovalsFG, LPCB, CPR

Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.

Request a site survey and quote for your project

Tell us about your building, existing system and requirements; together, we can determine the right solution.

WhatsApp SupportMessage us