Apollo ORB-HT-11002-APO A2S Heat Detector
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFDatasheetOrbis Heat Detector Datasheet
EnglishIncludes a wiring diagramPDFInstallation Manual
Orbis Detector Head Installation Manual
EnglishIncludes a wiring diagramPDFCertification
LPCB Certificate
EnglishPDFCertification
FG Certificate
EnglishPDFOther Document
Orbis Engineering Product Guide
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
The Orbis A2S heat detector monitors ambient temperature using a single thermistor. It can be used in dusty or normally smoky environments where smoke detectors are unsuitable. It indicates operation with a red LED at start-up and signals a fault with the yellow SensAlert® LED.
Key features
- Class A2S heat rating
- For applications where smoke detectors are unsuitable
- Suitable for dusty or normally smoky environments
- Red LED indication at start-up
- Yellow SensAlert® LED fault indication
- Four-second functional test with FasTest®
Technical specifications
| Heat class | A2S |
|---|---|
| Suitable fire type | Fast-burning, flaming fires |
| Standby current | 95 μA (tested at 24 V DC) |
| Operating voltage | 5–33 V |
| Operating temperature | -40 to 70 °C |
| Protection rating | IP23D |
| Colour | White |
| Weight | 70 g |
| Dimensions | 97 mm diameter, 36 mm length |
| Warranty | 10 years |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other Apollo products

Apollo 29600-929 Conventional End-to-End Beam Detector

Apollo 29650-069 Self-Aligning Conventional Reflective Beam Detector

Apollo 29650-081APO Single-Point Aspirating Smoke Detector

Apollo 29650-082APO Dual-Point Aspirating Smoke Detector
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.