Apollo ORB-OH-43001-MAR Orbis Marine Optical/Heat Multisensor Detector
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFDatasheetOrbis Marine Multisensor Detector Datasheet
EnglishIncludes a wiring diagramPDFCertification
DNV Certificate
EnglishPDFCertification
Lloyd's Register Certificate
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
Designed for marine applications, this detector combines optical sensing with a heat-sensing element. It responds to fast- and slow-burning fires; its design helps reduce false alarms by preventing dust and other airborne contaminants from entering the sensing chamber.
Key features
- Optical and heat detection
- Responds to fast- and slow-burning fires
- Technology that helps reduce false alarms
- Contaminant-protected sensing chamber
- Operates across a wide voltage range
- -40 to 70 °C operating temperature
Technical specifications
| Applications | Marine applications, bedrooms, dusty environments |
|---|---|
| Detection principle | Photoelectric light scattering |
| Sensing chamber | Chevron type |
| Standby current | 95 μA (tested at 24 V DC) |
| Hold voltage | 5–33 V |
| Operating temperature | -40 to 70 °C |
| Humidity range | 0–98%, without condensation or icing |
| Protection rating | IP44 |
| Dimensions | 97 mm diameter, 42 mm length/height (without base) |
| Weight | 80 g |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other Apollo products

Apollo 29600-929 Conventional End-to-End Beam Detector

Apollo 29650-069 Self-Aligning Conventional Reflective Beam Detector

Apollo 29650-081APO Single-Point Aspirating Smoke Detector

Apollo 29650-082APO Dual-Point Aspirating Smoke Detector
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.