Apollo SA4700-300APO Intelligent DIN-Rail Contact Monitoring Module
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFDatasheetSmart DIN Rail Contact Monitoring Module Datasheet
EnglishIncludes a wiring diagramPDFInstallation Manual
Smart DIN Rail Contact Monitoring Module Installation Manual
EnglishIncludes a wiring diagramPDFCertification
SBSC Certificate
EnglishPDFCertification
BOSEC Certificate
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
Monitors one or more single-pole, voltage-free contacts and transmits status information to the fire alarm control panel. Offers a selectable input delay for monitoring flow switches and can be mounted on a DIN rail. Compatible with XP95, Discovery and CoreProtocol systems.
Key features
- Certified to EN 54-17 and EN 54-18
- Priority and non-priority setting options
- Selectable input delay for flow switches
- Suitable for DIN rail mounting
- Compatible with XP95, Discovery and CoreProtocol
- Design for easy wiring and installation
Technical specifications
| Supply voltage | 17–35 V DC |
|---|---|
| Protocol voltage | 5–13 V peak-to-peak |
| Standby current | 500 µA |
| Dimensions | 33 × 102 × 33 mm |
| Weight | 43,5 g |
| Colour | White |
| Operating temperature | −40 to 70 °C |
| Relative humidity | %0–95, non-condensing and frost-free |
| Standards | EN 54-17, EN 54-18 |
| Warranty | 10 years |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other Apollo products

Apollo 29600-378 Conventional I.S. Galvanic Barrier

Apollo 29600-442 Conventional I.S. AV Galvanic Barrier

Apollo 55000-181MAR XP95 Marine DIN-Rail Audible/Visual Alarm Control Module (8 A)

Apollo 55000-182APO DIN-Rail Audible-Visual Warning Control Module
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.