Aritech 2010-1-SB Supervised Output Card
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFDatasheet2010-1-SB Datasheet (English)
EnglishPDFInstallation Manual
2010-1-SB Installation Manual (English)
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
The 2010-1-SB provides four programmable, supervised outputs for the 2010-1 conventional fire alarm panel. The outputs can be configured to operate according to the panel's alarm status or the status of selected detection zones.
Key features
- Four polarity-reversing supervised outputs
- Powered from the panel bus and installed inside the panel without additional wiring
- Delay settings for each output
- AND and OR programming functions
- Expands notification circuits and alarm signalling
Technical specifications
| Supply voltage | 24 VDC |
|---|---|
| Current consumption | 30 mA standby; 1 A active |
| Number of outputs | 4 |
| Relay value when powered by the panel | Max. 250 mA per output; 300 mA total across all outputs |
| Relay value when externally powered | Max. 250 mA per output |
| Dimensions | 127 x 76 mm (Ø x D) |
| Net weight | 48 g |
| Mounting type | Inside the enclosure |
| Operating temperature | -5 to +40 °C |
| Storage temperature | -5 to +70 °C |
Information has been compiled from the manufacturer's source. Please refer to the manufacturer's documentation for current technical specifications.
Other Aritech products

Aritech 2010-1-NB RS485 Network Interface Card

Aritech 2010-1-RB Unsupervised Relay Card
Aritech 2010-1X-AE Conventional Fire Panel Fire Suppression Accessory

Aritech 2010-2-232-KIT Fire Panel RS232 Kit
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.