This addressable fire panel set provides detection and alarm management with two high-power loops and a user interface without fire brigade controls. Loop power can be increased to 800 mA; the panel also supports UltraSync cloud communication.
Key features
- 2 high-power loops, expandable to 4 loops with an additional card
- Loop power can be increased from 500 mA to 800 mA using a PAK
- Capacity for up to 512 zones and 300 output groups
- 40-zone fire/fault LED indication
- Cloud communication via the EN 54-21 UC240 UltraSync communication device
- Supports upgrades to existing systems with backward compatibility
Technical specifications
| Maximum number of loops | 4 |
|---|---|
| Loop current | 500 mA; expandable to 800 mA |
| Maximum zone capacity | 512 |
| Network capacity | Up to 64 nodes |
| Operating voltage | 110 / 240 VAC (+10%/−15%) |
| Battery capacity | Max. 2 × 12 V, 18 Ah |
| Dimensions | 446 × 536 × 164 mm |
| Net weight | 7,4 kg (excluding batteries) |
| Colour | White |
| Mounting type | Surface mounting |