Monday – Friday 09:00 – 18:00Service across Türkiye
Request a Survey / Quote TR
Aritech 2X-AF1-19 1-Loop Addressable Fire Alarm Panel (Turkish)
Aritech · Fire Panels

Aritech 2X-AF1-19 1-Loop Addressable Fire Alarm Panel (Turkish)

Brand
Aritech
Model
2X-AF1-19
Product type
Aritech Fire Alarm Control Panel
Category
Fire Panels
Other spellings
2XAF119, 2X AF1 19
System Type
Addressable

Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.

Product description

1. Product Name: Aritech 2X-AF1-19 1-Loop Addressable Fire Alarm Panel (Turkish)

2. Description:

What Is the Aritech 2X-AF1-19 Addressable Fire Alarm Panel?

Aritech 2X-AF1-19 is an addressable fire alarm control panel in the 2X-A series, featuring a single high-power loop and a Turkish user interface. It is designed to meet the need for intelligent detection and rapid response in small and medium-sized buildings. Aritech fire products are now also offered by Carrier under the Kidde Commercial brand.

Operating Principle

The panel continuously polls up to 128 addressable devices (detectors, manual call points and modules) on a single loop and can group them into up to 512 zones in software. When a device reports an alarm or fault, the event is displayed on the graphic screen and LEDs, and the programmed output groups (up to 300) are activated. Standard features include 2 supervised sounder/fire routing output, 2 relays operating as a pair for common fire and fault indications, 2 supervised output and 2 user-defined inputs for monitoring and control.

Role in Fire Detection Systems

2X-AF1-19 is the hub of the addressable system: it evaluates data from detectors, makes alarm decisions and controls outputs such as sounders, beacons and fire brigade signalling. With an optional network card, it can connect to a network, making it a flexible starting point for growing projects.

Why Choose It?

  • High-power loop: Provides 500 mA per loop; this can be increased to 800 mA with an optional power pack, readily supporting loop-powered sounders and beacons.
  • Easy operation: Icon-based graphical LCD, jog dial with 4 soft keys and a 3-level menu (20 users) simplify operation.
  • Remote access and integration: Ethernet enables remote diagnostics and programming, e-mail notifications (4 accounts), UltraSync cloud connectivity via UC240 and ATS8600 integration.
  • Backward compatibility: Compatible with existing 2X series devices, panels and repeaters, preserving infrastructure in modernisation projects.
  • Logging and reporting: Includes 9999 event log, 3 USB port and RS232 printer connection.

Installation and Commissioning

The panel is suitable for surface mounting in its painted steel enclosure and must be used indoors. The easily removable cover and chassis, along with fully pluggable connectors, make wiring neat and quick. The recommended loop cable is a 2-core, 1,5 mm² twisted pair, and the loop length must not exceed 2 km. The enclosure can accommodate up to 2 × 12 V / 18 Ah backup batteries. Automatic configuration and setup wizards speed up commissioning. Work should be carried out in accordance with EN54 and local regulations.

Technical Specifications

  • User interface: Turkish, without fire brigade controls
  • Network capacity: Default 32 nodes/32 loops; 2010-2-PAK-NET256 enables 64 nodes/256 loops
  • Operating voltage: 110/240 VAC (+10%/−15%), 50/60 Hz
  • Mains current: Max. 1,6 A (240 VAC)/2,8 A (110 VAC)
  • Loop capacity: 1
  • Loop current: 500 mA (2010-2A-PAK-HPL: 800 mA), 17-28 VDC
  • Loop cable: 2 x 1,5 mm² twisted pair; 52 ohm / 500 nF; max. 2 km
  • Zone capacity: up to 512
  • Inputs: 2 programmable, monitored, max. 150 mA
  • Fire / fault outputs: 350 mA / 21-28 VDC (24 VDC nominal)
  • Programmable outputs: 2 Class B/1 Class A, max. 750 mA
  • Auxiliary power output: 1 resettable outputs, 500 mA
  • Backup battery: Max. 2 x 12 V / 18 Ah
  • Dimensions / weight: 446 x 536 x 164 mm (W x H x D) / 9,8 kg (excluding batteries)
  • Colour / material: White (RAL 9003) / painted steel, surface-mounted
  • Operating temperature / humidity: -5 to +40°C / 10-95% non-condensing
  • Protection rating: IP30, indoor use
  • Standards: EN54-2, EN54-4, EN54-13, EN54-21; CPR, CE, RoHS 3, WEEE

Applications

  • Office and commercial buildings
  • Hotels, student accommodation and residential projects
  • Schools, university campuses and hospitals
  • Shopping centres and retail chains
  • Factories, warehouses and logistics facilities
  • Multi-building campuses and residential complexes

Compatible Products

The panel works with Aritech 2000 series addressable detectors with replaceable optical chambers (DP2061N optical, DT2063N heat, DP2061T multisensor) and 2000 series DB2002, DB2004, DB2016 bases. The 2010-2-NB network card can be used for networking, the 2X-ZI-40 LED indicator card for separate zone indication, and the 2X-AFR-19 repeater panel for monitoring at remote locations.

Frequently Asked Questions

How many devices does the 2X-AF1-19 support? A single high-power loop supports up to 128 addressable devices and programming for up to 512 zones.

What does the -19 code mean? The -19 suffix in the product code indicates that the panel has the Turkish-language version and user interface.

Can the panel be networked? Yes. An 2010-2-NB network card can be added to connect the panel to the same network as other 2X series panels and repeaters.

At Narstek, we provide project support for Aritech 2X-A series addressable fire alarm panels, including product selection, system design, programming and commissioning. Contact us for technical information and a quote.

Request a site survey and quote for your project

Tell us about your building, existing system and requirements; together, we can determine the right solution.

WhatsApp SupportMessage us