Aritech Excellence KE-IO3122 Addressable 2-Input / 2-Output Module with Isolator
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFDatasheetKE-IO3122 Datasheet (English)
EnglishPDFInstallation Manual
KE-IO3122 Installation Manual (English)
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
KE-IO3122 is a two-input, two-relay-output interface module powered by the Kidde Excellence addressable loop. It monitors contacts and controls equipment; its integrated short-circuit isolator, local test facility and status indicators support installation and maintenance.
Key features
- Two separate programmable inputs and outputs on a single address
- Two-level supervised inputs with pre-alarm and alarm monitoring
- Integrated short-circuit loop isolator
- Normally open or normally closed contact selection
- Local test and three-colour LED status indicators
Technical specifications
| Number of inputs | 2 |
|---|---|
| Number of outputs | 2 |
| Output type and rating | Relay, 2 A at 30 VDC (resistive load) |
| Supply type | Loop-powered |
| Operating voltage | 17–29 VDC |
| Current consumption | 300 µA at 24 VDC (standby); 2,5 mA (active) |
| Address range | 1–128 |
| Dimensions | 148 × 102 × 27 mm (W × H × D) |
| Isolation type | Negative line break |
| Standards | EN54-17, EN54-18 |
Information has been compiled from the manufacturer's source. Please refer to the manufacturer's documentation for current technical specifications.
Other Aritech products

Aritech Excellence KE-IO3001 Addressable Relay Output Module

Aritech Excellence KE-IO3001-M Addressable Mains Switching Relay Module

Aritech Excellence KE-IO3044 Addressable 4-Input / 4-Output Module

Aritech Excellence KE-IO3101 Addressable Relay Output Module with Isolator
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.