C-TEC BF354 EN54-13 Interface Card
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualBF354 Interface Card Installation Instructions
EnglishPDFCatalogue
EN54-13 Conventional Fire System Brochure (UK)
EnglishPDFCatalogue
EN54-13 Conventional Fire System Brochure (Netherlands)
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
BF354 is installed inside CFP conventional fire alarm panels with 2–8 zones to provide two monitored sounder circuits. Compliance with EN54-13 is approved by BSI. When used with the BF355 fault monitoring module, it can monitor open- and short-circuit faults on the sounder circuits.
Key features
- BSI-certified to EN54-13
- Two conventional sounder circuits
- Fits CFP panels with 2–8 zones
- Circuit fault monitoring with BF355
- Detects sounder circuit resistance of up to 10 Ω
Technical specifications
| Number of sounder circuits | 2 |
|---|---|
| End-of-line resistor | 6800 Ω, 5% tolerance |
| Alarm voltage | Max. 27 VDC, min. 20 VDC |
| Maximum sounder output current | 2 × 400 mA (800 mA total) |
| Dimensions | 80 × 124 × 9 mm |
| Certification | BSI-approved to EN54-13 |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.