C-TEC BF560-12/E 12 V 2 A EN54-4/A2 Power Supply
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualBF560-12/E Installation Instructions (DFU0056012)
EnglishPDFCertification
5 Series Power Supplies EU Declaration of Conformity
EnglishPDFCertification
5 Series Power Supplies UKCA Declaration of Conformity
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
BF560-12/E is a switch-mode power supply that converts mains electricity to a 12 V DC output, with a capacity of 2 A. It contains electronics that comply with EN54-4/A2 requirements for use in fire alarm systems and reports faults via a relay. Its metal base plate allows installation inside suitable third-party enclosures.
Key features
- 12 V DC output, total current limit of 2 A
- Single-pole volt-free relay with contacts switched in the event of a fault
- Fault and hazardous voltage indicators
- Two selectable battery charging currents
- Battery resistance and other settings can be customised using the BF423 configurator
- Optional remote thermistor connection
Technical specifications
| Mains supply | 230 V, 50/60 Hz |
|---|---|
| Mains rated current | 300 mA rms |
| Maximum total output current | 2 A |
| Output current | Imax.a: selectable 1,8 A or 1,3 A; Imax.b: 2 A |
| Battery capacity | 2 Ah–12 Ah |
| Battery type | VRLA up to 12 Ah; depending on enclosure size |
| Dimensions | 103 × 173 × 53 mm |
| Operating temperature | -5 °C to +40 °C |
| Protection rating | Depending on mounting enclosure |
| Weight | 324 g (excluding batteries) |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.