C-TEC CA430A/SR CAST High-Output Wall Sounder, Shallow Base
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualCAST High Output Sounder and VAD Installation Instructions
EnglishPDFCertification
CA430A/SR Shallow Base High Output Wall Sounder EU Certificate of Conformity
EnglishPDFCertification
CA430A/SR Shallow Base High Output Wall Sounder UKCA Certificate of Conformity
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
This wall-mounted sounder is compatible with C-TEC CAST addressable fire alarm systems and is designed for indoor use. It provides a sound output of 100 dB(A) at 1 metres and offers four volume levels and 31 tone options. It features an integral short-circuit isolator and group addressing.
Key features
- 1 dB(A) sound output at 100 metres
- 4 selectable volume levels and 31 tones
- Built-in short-circuit isolator
- Group addressing feature
- IP21C ingress protection rating
- Compatible with the C-TEC CAST protocol
Technical specifications
| Supply voltage | 24–40 V DC |
|---|---|
| Standby current | Typical 460 µA |
| Alarm current | Typical 6,5 mA (at maximum volume) |
| Nominal sound pressure level | 100 dB(A), Tone setting 1 |
| Dimensions | 108 mm diameter × 99 mm depth |
| Protection rating | IP21C (Type A) |
| Weight | 215 g |
| Operating temperature | -10 °C to +55 °C |
| Humidity | Maximum 95%, non-condensing |
| Installation | Wall-mounted; indoor use only |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC 45681-509APO AlarmSense Base Sounder and Visual Indicator

C-TEC 45681-510APO AlarmSense Base Sounder

C-TEC 55000-017APO AlarmSense Outdoor Sounder/Beacon

C-TEC 55000-018APO IP65 Outdoor Fire Sounder
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.