C-TEC CA450A/SW CAST Compact 96 dB Ceiling Sounder
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualCAST Compact Sounder Installation Instructions
EnglishPDFCertification
CAST CA450A/SW and CA450A/SR Compact Sounder EU Declaration of Conformity
EnglishPDFCertification
CAST CA450A/SW and CA450A/SR Compact Sounder UKCA Certificate of Conformity
EnglishPDFOther Document
CAST Compact Sounder Polar Diagrams
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
A compact sounder compatible with C-TEC CAST addressable fire alarm systems, suitable for ceiling or wall mounting. On tone 1, it delivers 96 dB(A) at a distance of 1 metres; selectable volume and tone options are available for different applications.
Key features
- Compatible with the CAST protocol
- 96 dB(A) nominal sound level at a distance of 1 m
- 4 selectable volume levels and 31 selectable tones
- Integral short-circuit loop isolator
- Suitable for ceiling or wall mounting
- IP21C ingress protection rating
Technical specifications
| Supply voltage | 24–40 V DC |
|---|---|
| Standby current | Typical 460 µA |
| Alarm current | 5,5 mA at maximum volume |
| Nominal sound pressure level | 96 dB(A) on tone 1, at a distance of 1 m |
| Dimensions | 102 mm diameter × 63 mm depth |
| Protection rating | IP21C (Type A) |
| Weight | 160 g |
| Operating temperature | -10 °C to +55 °C |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC 45681-509APO AlarmSense Base Sounder and Visual Indicator

C-TEC 45681-510APO AlarmSense Base Sounder

C-TEC 55000-017APO AlarmSense Outdoor Sounder/Beacon

C-TEC 55000-018APO IP65 Outdoor Fire Sounder
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.