C-TEC CA451A/SW Compact C-3-8 Ceiling Sounder with VAD
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualCAST Compact Sounder Instructions
EnglishPDFCertification
EU CPR Certificate of Conformity for CA451A/SW and CA451A/SR Compact Sounder VAD
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
Compatible with CAST addressable fire alarm systems, this device combines an audible alarm with a white visual alarm signal. When ceiling-mounted, it provides a C-3-8 coverage class; when wall-mounted, W-3-3.1. It features a short-circuit isolator, selectable sound levels and tones.
Key features
- 96 dB(A) sound output (at 1 m, tone 1)
- Coverage: C-3-8 for ceiling mounting; W-3-3.1 for wall mounting
- White light with a flash frequency of 0,5 Hz
- 4 selectable volume levels and 31 tones
- Integral short-circuit loop isolator
- Group addressing feature
Technical specifications
| Compatible system | C-TEC CAST addressable fire panels |
|---|---|
| Supply voltage | 27–40 V DC |
| Standby current | Typical 460 µA |
| Alarm current | 12,5 mA (VAD on, sounder at maximum volume) |
| Nominal sound pressure level | 96 dB(A) at tone 1 |
| VAD coverage class | C-3-8 or W-3-3.1 |
| Flash frequency and colour | 0,5 Hz / white |
| Protection rating | IP21C (Type A) |
| Dimensions | 102 mm diameter × 63 mm depth |
| Operating conditions | -10 °C to +55 °C; up to 95% relative humidity (non-condensing) |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC 45681-509APO AlarmSense Base Sounder and Visual Indicator

C-TEC 45681-510APO AlarmSense Base Sounder

C-TEC 55000-017APO AlarmSense Outdoor Sounder/Beacon

C-TEC 55000-018APO IP65 Outdoor Fire Sounder
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.