C-TEC FF388-2 8-zone Conventional Fire Alarm Panel
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFWiring DiagramFF374X Wiring Harness Instructions
EnglishPDFInstallation Manual
FP 2–14 Zone Fire Panel Guide
EnglishPDFInstallation Manual
BF378M Instructions
EnglishPDFInstallation Manual
FF374-FR Fault Relay Module Instructions
EnglishPDFInstallation Manual
FF374-DFR Fire Relay Module Instructions
EnglishPDFInstallation Manual
FF374-DT Delay Timer Module Instructions
EnglishPDFInstallation Manual
FP Fire Repeater Panel Instructions
EnglishPDFInstallation Manual
FF387Z-2 Two-Zone Expansion Card Instructions
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
C-TEC FF388-2 is a fire alarm control panel with eight conventional zone circuits, expandable to 14 zones using expansion cards. It is designed to monitor fire detection zones and two sounder circuits. The manufacturer states that the panel meets BS 5839-4 requirements, is not compliant with EN54-2/4, and should not be used in new UK or European installations.
Key features
- 8 zone circuits; expandable to 14 zones with expansion kits
- Two conventional sounder circuits
- Separate indicators for open-circuit, short-circuit, sounder and power supply faults
- Internal space for 2 12 V 7 Ah VRLA batteries
- Connections for repeaters and additional system modules
- Metal enclosure and keyed controls
Technical specifications
| Mains supply | 230 V, 50/60 Hz |
|---|---|
| Number of zone circuits | 8; up to 14 with FF387Z-2 expansion kits |
| Number of sounder circuits | 2 |
| Maximum cable length per zone circuit | 500 m |
| Maximum cable length per sounder circuit | 500 m |
| Maximum number of detectors | 20 per zone; maximum detector current 2 mA |
| Battery | 2 × 12 V 7 Ah VRLA batteries connected in series |
| Dimensions | 521 × 334 × 140 mm (W × H × D) |
| Protection rating | IP30 |
| Operating temperature | −5 °C to +40 °C |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC CFP702-2 2-Zone Two-Wire AlarmSense Fire Alarm Control Panel

C-TEC CFP702-4 2-zone Conventional Fire Alarm Panel

C-TEC CFP704-2 4-zone Two-Wire AlarmSense Conventional Fire Alarm Panel

C-TEC CFP704-4 4-zone Conventional Fire Alarm Panel
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.