C-TEC FF388-3 8-zone Economy Conventional Fire Alarm Panel
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualFPE8 8 Zone Fire Panel User and Installation Manual
EnglishPDFInstallation Manual
BF378M Minimum Instructions
EnglishPDFInstallation Manual
FF374X Wiring Harness Instructions
EnglishPDFInstallation Manual
FF374-FR Fault Relay Module Instructions
EnglishPDFInstallation Manual
FF374-DFR Fire Relay Module Instructions
EnglishPDFInstallation Manual
FF374-DT Delay Timer Module Instructions
EnglishPDFInstallation Manual
FP Fire Repeater Panel Instructions
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
The FF388-3 is a conventional fire alarm control panel with eight detection zones and two sounder circuits. Its metal enclosure provides separate indicators for zone, sounder and power supply faults; it can be used with repeaters and additional modules. The manufacturer states that the panel was designed to meet the requirements of BS 5839-4 but is not compliant with EN54-2/4 and should not be used in new UK or European installations.
Key features
- 8 conventional detection zone; expandable to 12 zones with an expansion kit
- 2 conventional sounder circuits
- Separate indicators for open-circuit, short-circuit, sounder and battery/power supply faults
- Space for two 12 V 3,2 Ah VRLA batteries
- Compatible with repeaters and optional expansion modules
- Metal enclosure with cover and base
Technical specifications
| Mains supply | 230 V, 50/60 Hz |
|---|---|
| Maximum mains current | 330 mA |
| Internal power supply | 27 V nominal |
| Battery | 2 × 12 V 3,2 Ah VRLA batteries connected in series |
| Maximum cable length per zone | 500 m |
| Maximum number of detectors per zone | 20 per zone; maximum current per detector 2 mA |
| Number of sounder circuits | 2; maximum cable length per circuit 500 m |
| Maximum sounder output current | 1400 mA for all outputs; outputs are fused at 1 A |
| Dimensions | 405 × 267 × 92 mm |
| Ingress protection rating and operating temperature | IP30; -5 °C to +40 °C |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC CFP702-2 2-Zone Two-Wire AlarmSense Fire Alarm Control Panel

C-TEC CFP702-4 2-zone Conventional Fire Alarm Panel

C-TEC CFP704-2 4-zone Two-Wire AlarmSense Conventional Fire Alarm Panel

C-TEC CFP704-4 4-zone Conventional Fire Alarm Panel
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.