C-TEC FF390-2 10-zone Conventional Fire Alarm Panel
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFWiring DiagramFF374X Wiring Harness Instructions
EnglishPDFInstallation Manual
FP 2–14 Zone Fire Panel User and Installation Manual
EnglishPDFInstallation Manual
BF378M Minimum Instructions
EnglishPDFInstallation Manual
FF374-FR Fault Relay Module Instructions
EnglishPDFInstallation Manual
FF374-DFR Fire Relay Module Instructions
EnglishPDFInstallation Manual
FF374-DT Delay Timer Module Instructions
EnglishPDFInstallation Manual
FP Fire Repeater Panel Instructions
EnglishPDFInstallation Manual
FF387Z-2 Two-Zone Expansion Card Instructions
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
The FF390-2 is a fire alarm control panel with 10 zone circuits for conventional fire detection systems, expandable to 14 zones using two-zone expansion cards. It has two sounder circuits and separate indicators for different fault types. Its metal enclosure is designed for use in fire alarm systems in commercial and similar applications.
Key features
- 10 zone circuits; expandable to 14 zones
- Two conventional sounder circuits
- Separate indicators for open-circuit, short-circuit, sounder and power supply faults
- Internal space for two 12 V 7 Ah VRLA batteries
- Connections for repeaters and additional modules
- Metal enclosure with cover and base
Technical specifications
| Number of zone circuits | 10; up to 14 with FF387Z-2 expansion cards |
|---|---|
| Number of sounder circuits | 2 |
| Mains supply | 230 V, 50/60 Hz |
| Internal power supply | 27 V nominal |
| Battery | 2 × 12 V 7 Ah VRLA batteries connected in series |
| Maximum sounder output current | Total of 3000 mA across all outputs; outputs fused at 1 A |
| Product dimensions | 521 × 334 × 140 mm |
| Protection rating | IP30 |
| Operating temperature | −5 °C to +40 °C |
| Weight | 9,2 kg |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC CFP702-2 2-Zone Two-Wire AlarmSense Fire Alarm Control Panel

C-TEC CFP702-4 2-zone Conventional Fire Alarm Panel

C-TEC CFP704-2 4-zone Two-Wire AlarmSense Conventional Fire Alarm Panel

C-TEC CFP704-4 4-zone Conventional Fire Alarm Panel
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.