C-TEC FF508 8-zone Conventional Fire Alarm Panel
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documents and wiring diagrams
PDFWiring DiagramFF574X Wiring Harness Installation Instructions
EnglishPDFInstallation Manual
FF501Z 4-Zone Expansion PCB Installation Instructions
EnglishPDFInstallation Manual
MFP Fire Repeater Panel Installation Instructions
EnglishPDFUser Manual
MFP 4–28 Zone Fire Panel User Manual
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
FF508 is a fire alarm control panel for conventional fire detection systems, with 8 zone circuits. The number of zones can be increased to 12 using the FF501Z expansion board kit. The metal-cased panel provides four sounder circuits and separate fault indicators.
Key features
- 8 zone circuits; expandable to 12 zones using the FF501Z kit
- 4 conventional sounder circuits
- Separate fault indicators for open circuits, short circuits and detector removal
- Fire and fault outputs via the optional FF574X wiring harness
- Compatible with up to 8 two-wire repeaters
- Space for 2 12 V 3,2 Ah VRLA batteries
Technical specifications
| Number of zone circuits | 8; expandable to 12 using the FF501Z kit |
|---|---|
| Number of sounder circuits | 4 |
| Mains supply | 230 V, 50/60 Hz |
| Internal power supply | 27 V nominal |
| Battery | 2 × 12 V 3,2 Ah VRLA batteries connected in series |
| Maximum number of detectors per zone | 20; detector current up to 2 mA |
| Maximum zone circuit length | 500 m |
| Dimensions | 405 × 267 × 92 mm |
| Protection rating | IP30 |
| Operating temperature | -5 °C to +40 °C |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC CFP702-2 2-Zone Two-Wire AlarmSense Fire Alarm Control Panel

C-TEC CFP702-4 2-zone Conventional Fire Alarm Panel

C-TEC CFP704-2 4-zone Two-Wire AlarmSense Conventional Fire Alarm Panel

C-TEC CFP704-4 4-zone Conventional Fire Alarm Panel
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.