C-TEC XFP501E/H 1-loop, 16-zone Addressable Fire Alarm Panel
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Technical documentation
PDFInstallation ManualXFP Apollo/Hochiki Single-Loop 16-Zone Fire Panel Engineering Manual
EnglishPDFUser Manual
XFP Apollo/Hochiki Fire Panel User Manual
EnglishPDFCertification
XFP501E/H Fire Panel EU Declaration of Conformity
EnglishPDFCertification
XFP Hochiki Fire Panels EU Declaration of Conformity
English
The manufacturer has not published Turkish documentation for this product; please contact us for technical support in Turkish.
Product description
The C-TEC XFP501E/H is a single-loop, 16-zone addressable fire alarm panel using the Hochiki ESP protocol. It is suitable for small, standalone applications or larger systems with up to eight XFP master panels networked together. It is certified by LPCB to EN54-2 and EN54-4.
Key features
- Compatible with the Hochiki ESP protocol
- Up to 126 addressable devices on one loop
- Two programmable conventional sounder circuits
- Two programmable inputs and three programmable relays
- 999 event log
- Network up to eight XFP master panels using an optional card
Technical specifications
| Certification | LPCB; EN54-2 and EN54-4 |
|---|---|
| Supply | 230 V AC, 50/60 Hz |
| Internal power supply | 27 V DC nominal |
| Number of loops | 1 |
| Number of addressable devices per loop | Max. 126 |
| Maximum loop current | 500 mA |
| Maximum loop length | 1 km |
| Standby battery | Series-connected 2 × 12 V, 3,2 Ah VRLA batteries |
| Dimensions | 380 × 235 × 96 mm |
| Protection rating | IP30 |
Information has been compiled from manufacturer/distributor sources. Please consult the documentation for current technical specifications.
Other C-TEC Products

C-TEC CFP702-2 2-Zone Two-Wire AlarmSense Fire Alarm Control Panel

C-TEC CFP702-4 2-zone Conventional Fire Alarm Panel

C-TEC CFP704-2 4-zone Two-Wire AlarmSense Conventional Fire Alarm Panel

C-TEC CFP704-4 4-zone Conventional Fire Alarm Panel
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.