DetectomatHSSD2 MSee the datasheet for the product image
Detectomat · Detectors
Detectomat HSSD2 M Laser Aspirating Detector without Display
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Product description
Detectomat HSSD2 M is a screenless laser air sampling detector designed for early fire detection in sensitive or heavily contaminated environments. Its intelligent algorithm and dust separation technology adapt to ambient conditions and help reduce nuisance alarms.
Key features
- Intelligent automatic adjustment and learning modes to adapt to ambient conditions
- Patented Dual Technology LDD 3D3 laser dust separation and removal system to reduce nuisance alarms caused by dust
- Automatic day/night mode for different ambient conditions
- Integrated technology and dust filter to help mitigate the effects of contamination
- 4 sampling pipe and 1 return pipe to equalise pressure differences
- Network connection for up to 127 participants via RS 485
- Alarm and fault signalling via external potential-free relay outputs
- Product 31 will be discontinued as of December 2025; the final order date is September 30 2025. From January 2026 onwards, only remaining stock and warranty replacements will be available. ModuLaser aspirating smoke detectors are recommended as an alternative.
Technical specifications
| Supply voltage | External 21,6–26,4 V DC |
|---|---|
| Outputs | 5 potential-free relays for information, pre-alarm, Fire 1, Fire 2 and fault |
| Operating temperature | -10°C to +60°C |
| Maximum humidity | %90, non-condensing |
| Protection rating | IP 50 |
| Dimensions (H × W × D) | 372 × 427 × 95 mm |
| Weight | 5,2 kg |
| Material | Cast aluminium, ABS |
| Housing colour | Light grey |
| Standard | DIN EN 54-20 |
| Detection sensitivity | Adjustable between 0,002–25 % obs/m |
| Current consumption | 450 mA at 24 V DC |
| Particle sensitivity | 0,0003–10 µm |
| Pipe diameter | 3/4 inch |
| Sampling pipes | 4 pipe; maximum pipe length 250 m |
| Total pipe length | Up to 200 m; maximum 100 sampling holes |
| Maximum number of holes according to EN 54-20 class | Class C: 80; Class B: 60; Class A: 20 |
| Loop connection | Connection to Loop 3000 via the IOM |
| Approval | VdS G 203024 |
| Compatibility | DIN EN 54-13 |
Manufacturer's product number: 31867
From the same brand
More Detectomat products

Detectomat CT 3000 O Conventional Optical Smoke Detector
CT 3000 O Conventional

Detectomat CT 3000 OT Conventional Optical and Heat Multi-Sensor Detector
CT 3000 OT Conventional

Detectomat CT 3000 OTi Conventional Optical and Heat Multi-Sensor Detector
CT 3000 OTi Conventional

Detectomat CT 3000 T Conventional Heat Detector
CT 3000 T Conventional
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.