Detectomat · Call Points
Detectomat PL 3300 PBD-ALU-OD Smoke Ventilation Button
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Product description
Designed for Loop 3000, this smoke control manual call point activates an alarm manually when the front glass is broken. It features an integrated reset mechanism, a bidirectional isolator and a red LED to indicate the alarm condition.
Key features
- Manually activates the alarm when the front glass is broken
- Integrated reset mechanism
- Automatic and manual addressing via Loop 3000
- Integrated isolator and T-branch option
- Functions operate via the Loop 3000 protocol
- Integrated red LED for alarm indication
- OC output for a remote indicator or audible warning device
Technical specifications
| Supply voltage | 15–30 V DC (2-wire data bus) |
|---|---|
| Standby current | 280 µA |
| Alarm current | 280 µA; 5 mA when the alarm LED is activated |
| OC output | Max. 10 mA for a remote indicator or audible warning device |
| Operating temperature | −10 °C to +60 °C |
| Relative humidity | Max. 95% |
| Protection rating | IP42 |
| Dimensions (H × W × D) | 125 × 125 × 34 mm |
| Weight | Approx. 495 g |
| Material | Aluminium |
| Standard | EN 54-17 |
| Colour | Orange |
| Accessories | Replacement glass: 31910; replacement key: 40054 |
Manufacturer's product number: 31657
From the same brand
More Detectomat products

Detectomat CT 3000 PBD-ABS-B Blue Conventional Fire Call Point
CT 3000 PBD-ABS-B Conventional

Detectomat CT 3000 PBD-ALU Conventional Smoke Ventilation Call Point
CT 3000 PBD-ALU Conventional

Detectomat CT 3000 PBD-ALU-B Conventional Alarm Call Point
CT 3000 PBD-ALU-B Conventional

Detectomat CT 3000 PBD-ALU-Y Fire Suppression System Alarm Call Point
CT 3000 PBD-ALU-Y Conventional
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.