Detnov CAD-151-1 1-loop Addressable Fire Alarm Panel
Detnov · Fire Panels

Detnov CAD-151-1 1-loop Addressable Fire Alarm Panel

Brand
Detnov
Model
CAD-151-1
Product type
Detnov Fire Alarm Control Panel
Category
Fire Panels
Other spellings
CAD1511, CAD 151 1
System Type
Addressable

Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.

Product description

Detnov CAD-151-1 is a non-expandable, single-loop addressable fire alarm control panel supporting up to 250 addresses, which can be used for detectors, modules, sounders or manual call points. It offers a graphical LCD display, USB configuration and communication options for different systems.

Key features

  • Up to 250 addresses and 250 programmable zone
  • Automatic device search and self-diagnostics
  • Event log with a capacity of 6.000 events
  • Free configuration and maintenance software
  • Graphical LCD display and multilingual keypad
  • Connection via S-Network to up to 32 panels and repeaters
  • Compatible with Detnov Cloud and Detnov Remote Center

Technical specifications

Number of loops1; non-expandable
Maximum address capacity250
Supported addressable devicesDetectors, modules, sounders and manual call points
Number of programmable zones250
Alarm and fault zones indicated by LEDs20
Event log6.000 events
Sounder outputs2 monitored output
Relay outputs2, voltage-free and configurable via the board
Technical input1
Loop+ current per loopUp to 750 mA
Auxiliary output24 V
Configuration connectionUSB
Panel networkS-Network via RS485 or fibre optic; up to 32 nodes
Integration outputsContact-ID for Modbus and CMS connections
Remote connectivity compatibilityDetnov Cloud and Detnov Remote Center via TED-151-CL-CAN, TED-151-1PE-CAN, TMB-251-CAN or TCD-107NG KIT cards
External power supply optionOptional card for connecting the FAD-AUXBAT external power supply; backup time can be extended to up to 72 hours
EnclosureABS plastic; wall-mounted and suitable for recessed installation
CertificationsCPR EN 54-2, EN 54-4 and EN 54-13
BatteriesRequires 2 12 Ah batteries; not included
Dimensions436 × 270 × 125 mm