Detnov CCD-112 is a 12-zone conventional fire alarm panel with an ABS plastic enclosure and an optional flush-mounting installation. It distinguishes between detector alarms and manual call point alarms; it is programmable via USB and can be integrated directly into an addressable system loop.
Key features
- Up to 32 detectors can be connected to each zone.
- It distinguishes between detector alarms and manual call point alarms.
- Complex programming can be carried out by connecting it to a computer via USB.
- It can be integrated directly into the loop of an addressable system.
- It has two configurable, supervised sounder outputs.
- It has a multilingual keypad.
- Remote maintenance and control (Detnov Cloud) are available with the TED-151-CL card.
- A 4-supervised sounder output can be provided via TSD100, Modbus integration via TMD-100, Contact ID protocol for connection to a CRA via TCD, and addressable loop integration via TPLD-100.
Technical specifications
| Number of zones | 12 |
|---|---|
| Enclosure | ABS plastic |
| Installation | A recessed mounting option is available |
| Maximum number of detectors per zone | 32 |
| Sounder outputs | 2 configurable, supervised outputs; 500 mA each |
| Relay outputs | Volt-free relay outputs for alarm and fault |
| Auxiliary output | 24 V, maximum consumption 500 mA |
| Resettable output | 24 V, maximum consumption 500 mA |
| External input | 1 programmable input |
| Certifications | CPR; EN54-2, EN54-4 and EN54-13 |
| Dimensions | 443 × 268 × 109 mm |
| Required batteries | 2 x BTD-1207 batteries (not included) |