Eaton · Contact and Monitoring Modules
Eaton DIN01-OM DIN Rail Monitored Output Module
Request a quote for pricing and availability. Installation, commissioning and compatibility checks with your existing system are also available.
Product description
DIN01-OM integrates audible alarm devices in a conventional fire detection system into an addressable fire system. The module resets on alarm silence and reset commands.
Key features
- Soft-addressed and uses a single address
- Built-in short-circuit isolator
- Provides a conventional sounder circuit
- Requires an external regulated, current-limited power supply
- Reverse-polarity-monitored output
Technical specifications
| Certification | EN54 Parts 17 and 18 |
|---|---|
| Supply voltage | 20-30 V DC |
| Quiescent current | Maximum 3.4 mA |
| Quiescent load current | Maximum 2.8 mA |
| Alarm current | Maximum 8 mA |
| Output load | Maximum 1 A |
| Sounder circuit end-of-line resistor | 6K8 Ohm |
| Operating temperature | -10 °C to +55 °C |
| Protection rating | IP40 |
| Weight | 80 g |
| Height | 90,2 mm |
| Width | 36,3 mm |
| Depth | 57,5 mm |
| Reset behaviour | Using alarm silence and reset commands |
Information has been compiled from the manufacturer's source. Please refer to the manufacturer's documentation for current technical specifications.