Product description
The IQ8MCP has an IP66 protection rating and is suitable for use in damp areas. The integrated isolator supports esserbus and powered loop connections; the surface-mounting box and transparent cover are included.
Key features
- IP66 protection rating
- Integrated loop isolator
- Soft address coding and alarm latching
- Key-operated test, activation and reset functions
- Cable entries in the surface-mounting box for M20 cable glands
Technical specifications
| Operating voltage | 8–42 V DC |
|---|---|
| Standby current (at 19 V DC) | Approx. 45 µA |
| Alarm current (at 9 V DC) | Typically 18 mA |
| Number of detectors | 10 per zone; 127 per loop (according to VdS) |
| Status indicator | Green LED |
| Alarm indicator | Red LED and yellow flag |
| Connection terminal | Maximum 1,5 mm² (AWG 30-14) |
| Operating temperature | −20 °C to 70 °C |
| Protection rating | IP66 |
| Dimensions | 88 × 88 × 57 mm (with surface-mounting box) |
Information has been compiled from the manufacturer's source. Please refer to the manufacturer's documentation for current technical specifications.
From the same brand
Other Honeywell products

Honeywell ESSER 804906 Fire Alarm Call Point
804906 Addressable
Honeywell704800
Honeywell Esser 704800 Large Neutral Aluminium Manual Call Point Housing
704800

Honeywell Esser 704801.10 Large-Format Aluminium Manual Fire Call Point Enclosure with Break Glass
704801.10

Honeywell Esser 704804 Manual Call Point Enclosure with Break Glass Printed 'Home Alarm'
704804
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.