Kilsen KAL710 connects a conventional fire detector zone to an addressable fire system loop and reports the zone status to the panel. It is powered by an external 24 VDC supply and indicates local alarm and communication status via LEDs. Designed for surface mounting; addressed using DIP switches.
Key features
- Monitors 1 conventional fire zone
- Up to 20 detectors or 32 manual call points can be connected per zone
- Powered by an external 24 VDC supply
- Local alarm and communication status indicator
- Easy addressing via DIP switches
- EN54 and CPD certified
Technical specifications
| Number of zones | 1 |
|---|---|
| Detector capacity per zone | Up to 20 conventional detectors |
| Manual call point capacity per zone | Up to 32 conventional manual call points |
| Supply | External 24 VDC |
| Installation | Surface-mounted |
| Addressing | DIP switches |