Product description
KE-DP3120W is an addressable dual optical detector with an integrated short-circuit isolator for smoke detection. Automatic testing, a contamination warning and a three-colour 360° indicator help monitor system status; variants are available.
Key features
- Includes an integral loop short-circuit isolator.
- The remote indicator output is short-circuit protected.
- Dual optical detection helps distinguish unwanted alarms caused by steam and dust.
- Provides automatic testing and contamination monitoring.
- Three-colour indicator provides 360° visibility.
- Features rotary-switch addressing and event logging.
Technical specifications
| Compatibility | Kidde Commercial Excellence systems |
|---|---|
| Alarm threshold | 3 |
| Addressing method | Rotary switch |
| Operating voltage | 17–29 VDC |
| Current consumption | 200 μA (standby, 24 VDC); 4,75 mA (alarm, 24 VDC) |
| Detection principle | Forward and backward optical light scattering |
| Coverage area | < 112 m² |
| Number of devices per loop | Up to 128 |
| Dimensions | 100 × 47 mm (diameter × height) |
| Standard | EN54-7 |
Information has been compiled from the manufacturer's source. Please refer to the manufacturer's documentation for current technical specifications.
Other Aritech products

Aritech DP2061N Addressable Optical Smoke Detector

Aritech DP2061T Addressable Multisensor Detector (Optical-Heat)

Aritech DP721I Conventional Optical Smoke Detector

Aritech DP721R Conventional Optical Smoke Detector with Relay
Request a site survey and quote for your project
Tell us about your building, existing system and requirements; together, we can determine the right solution.